News

Video

What is the difference between pump gas detector and diffusion?
Views:136 Updated:2025-03-28
With Pump vs. Diffusion Gas Detector

1. Working Principle - Pump-Suction Type:
Uses a built-in air pump to actively draw gas samples into the detector for analysis, ensuring controlled sampling.
- Diffusion Type:
Relies on natural diffusion of ambient gas into the sensor, passively detecting environmental conditions. Performance may be affected by airflow, temperature, or humidity.



2.Key Differences
Comparison Criteria Pump-Suction Type Diffusion Type
Sampling Method Active pumping (mechanical suction) Passive diffusion (natural airflow)
Response Speed Fast (seconds to tens of seconds) Slower (minutes, dependent on airflow)
Applicable Scenarios Confined spaces (pipelines, tanks, tunnels), remote/hazardous area sampling Open areas (workshops, warehouses, labs)
Interference Resistance High (controlled airflow minimizes environmental impacts) Low (sensitive to wind, temperature, humidity)
Cost Higher (pump hardware and maintenance costs) Lower (simple design, minimal maintenance)
Portability Bulkier (due to integrated pump) Compact and lightweight
3. Scenario Recommendations
- Choose Pump-Suction When:
- Testing confined spaces (e.g., sewers, storage tanks, pipelines).
- Rapid detection is critical (e.g., emergency leak investigations).
- Remote sampling is required (using extended probes in hazardous zones).

- Choose Diffusion When:
- Monitoring open areas long-term (e.g., air quality in factories).
- Budget constraints or lightweight equipment is prioritized (daily inspections).
- Stable environments (no strong wind or extreme conditions).

4. Extended Considerations
Accuracy: Pump-suction types may offer better long-term stability by reducing sensor contamination.
Battery Life: Pump-suction detectors typically have shorter runtime due to pump energy consumption.
Maintenance: Pump-suction models require regular filter cleaning and potential pump replacements.

Pump-suction detectors excel in high-risk, confined, or time-sensitive scenarios, while diffusion types suit cost-effective monitoring in open, stable environments. Selection should balance detection needs, environmental factors, and budget constraints.
【Home】  【Return】
Prev:How to calibrate a gas detector?
Next:How far can a gas detector monitor?

TEL:18995278133ADD:Block A, Yinchuan Zhongguancun Innovation Center, Xingzhou Street, Xixia District, Yinchuan, Ningxia
Copyright©2025 Ningxia Maiya Sensor Technology Development Co., Ltd 宁ICP备2022001619号-1